Cap. 56activeordinance

Boilers and Pressure Vessels Ordinance

鍋爐及壓力容器條例

Full legislation

s.43

Pressure accumulation tests

(1)
Every pressure accumulation test to which a boiler is subjected for the purposes of this Ordinance shall be carried
out—
(a)
under full firing conditions;
(b)
with the feed water shut off; and
(c)
with the stop valves closed except to the extent that it is necessary for any stop valve to be open to supply steam to auxiliary equipment for the purposes of the test.
(Added
67 of 1978 s. 20
)
(2)
Every pressure accumulation test to which a
steam receiver is subjected for the purposes of this Ordinance shall be carried out at the maximum pressure of steam supply to which, with the stop valve or valves fully opened and any other plant or equipment that normally receives a supply of steam from the pipe or pipes supplying the steam receiver shut down, the steam receiver may be subjected when the boiler to which it is connected is being operated at the pressure that is or will be specified in the certificate of fitness issued in respect thereof as its maximum permissible working pressure.
(3)
Every pressure accumulation test to which an air receiver is subjected for the purposes of this Ordinance shall be carried
out—
(a)
at the maximum pressure that can be obtained in the compressor to which the air receiver is connected;
(b)
with the reducing valve or valves, or such other appliance as may be used to regulate the supply of compressed air to the air receiver, fully opened; and
(c)
with any other plant or equipment that normally receives a supply of air from the pipe or pipes supplying the air receiver shut down.